1. INSPECT REFRIGERANT VOLUME
(a) Check the sight glass on the cooler refrigerant liquid pipe A.
Test conditions:
Item |
Symptom |
Amount of refrigerant |
Corrective Actions |
1 |
Bubbles exist | Insufficient* | (1) Check for gas leakage and repair if necessary (2) Add refrigerant until bubbles disappear |
2 | No bubbles exist | Empty, insufficient or excessive | Refer to 3 and 4 |
3 | No temperature difference between compressor inlet and outlet | Empty or nearly empty | (1) Check for gas leakage with gas leak detector and repair if necessary (2) Add refrigerant until bubbles disappear |
4 | Considerable temperature difference between compressor inlet and outlet | Proper or excessive | Refer to 5 and 6 |
5 | Immediately after air conditioning is turned off, refrigerant clears | Excessive | (1) Discharge refrigerant (2) Remove air and supply proper amount of purified refrigerant |
6 | Immediately after air conditioning is turned off, refrigerant foams and then becomes clear | Proper |
- |
*: Bubbles in the sight glass with ambient temperatures higher than usual can be considered normal if cooling is sufficient.
2. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET
(a) This is a method in which the trouble is located by using a manifold gauge set. Read the manifold gauge pressure when these conditions are established.
Test conditions:
Gauge reading: Low pressure side: 0.15 to 0.25 MPa (1.5 to 2.5 kgf/cm2) High pressure side: 1.37 to 1.57 MPa (14 to 16 kgf/cm2)
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
During operation, pressure on low pressure side cycles between normal and vacuum | Moisture in refrigeration system
freezes at expansion valve orifice,
causing a temporary stop of cycle. However, when it melts, normal state is restored. |
|
|
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
Gas leakage in refrigeration system |
|
|
Symptom |
Probable cause |
Diagnosis |
Corrective Action |
|
Refrigerant flow is obstructed by dirt in the receiver | Receiver is clogged | Replace condenser |
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
|
Refrigerant does not circulate |
|
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
|
|
|
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
Air in system |
|
|
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
Trouble in expansion valve |
|
Check expansion valve |
Symptom |
Probable cause |
Diagnosis |
Corrective Actions |
|
Internal leak in compressor |
|
Repair or replace compressor |
Gauge readings (Reference)
Rear NO.2 Seat belt
COMPONENTS
REPLACEMENT
HINT:
The installation procedures are the removal procedures in reverse
order. However, only installation
procedures requiring additional information are included.
Use the same procedures for the RH side and LH side.
The procedures listed below are for the R ...